Difference between revisions of "LG"
Jump to navigation
Jump to search
Line 4: | Line 4: | ||
Master setting: {{Terminal | 1=>'''line master L7 <span style="color:#FF8080">1</span>'''<br>OK}} | Master setting: {{Terminal | 1=>'''line master L7 <span style="color:#FF8080">1</span>'''<br>OK}} | ||
Slave setting: {{Terminal | 1=>'''line master L7 <span style="color:#FF8080">0</span>'''<br>OK}} | Slave setting: {{Terminal | 1=>'''line master L7 <span style="color:#FF8080">0</span>'''<br>OK}} | ||
+ | |||
+ | == Setting Central Control Address == | ||
+ | Indoor Central Control Address is required for proper CoolMasterNet operation. Without Central Control Address Indoor unit is not visible and can not be controlled by CoolMasterNet. Address is set with wired remote controller. Here are a simple sequence of operations for different wired remote controllers. | ||
+ | * Models PQRCHCA0Q PQRCHCA0QW | ||
+ | [[File:BRC1E61-buttons.gif]] |
Revision as of 04:58, 12 August 2016
Connecting to LG VRF system
- CoolMasterNet has to be connected to the dedicated "Centralized Control Line" on Outdoor unit. It is not possible to connect to Indoor units. Centralized Control Line connectors on Outdoor unit are marked as CEN.A and CEN.B. If lines L3, L4, L5 or L6 are used in CoolMasterNet, make sure to connect CEN.A to A and CEN.B to B on CoolMasterNet side.
- Only two Control devices can be connected to the same Centralized Control Line. One of them must be Master and another - Slave. Thus, if any other control device, except CoolMasterNet, is connected to the same line make sure to separate them as Master/Slave. On CoolMasterNet Master/Slave settings can be done with below commands (assuming L7 is connected):
Master setting:
>line master L7 1 OK |
Slave setting:
>line master L7 0 OK |
Setting Central Control Address
Indoor Central Control Address is required for proper CoolMasterNet operation. Without Central Control Address Indoor unit is not visible and can not be controlled by CoolMasterNet. Address is set with wired remote controller. Here are a simple sequence of operations for different wired remote controllers.
- Models PQRCHCA0Q PQRCHCA0QW