Difference between revisions of "Midea"
Jump to navigation
Jump to search
Line 13: | Line 13: | ||
== Auto Addressing Mode == | == Auto Addressing Mode == | ||
− | For proper operation of the Central | + | For proper operation of the Central Controller (CoolMasterNet), it is important to have an '''Auto Addressing Mode''' turned on on Outdoor PCB. This is done by setting '''S6''' (on some models it is called NI_SD-AD_FD) DIP Switches to OFF-OFF-OFF positions like show on the below picture. |
[[File:Midea-dips.png]] | [[File:Midea-dips.png]] |
Revision as of 13:30, 16 December 2016
Connecting to Midea VRF system
- If CoolMasterNet is the only central controller in the system:
Outdoor Switch SW3-1 must be ON for proper operation of CoolMasterNet connected to XYE bus.
- If two central controllers should be connected:
We recommend to connect to line L7 on CoolMasterNet. Lines L4, L5, L6 can also be used.
Auto Addressing Mode
For proper operation of the Central Controller (CoolMasterNet), it is important to have an Auto Addressing Mode turned on on Outdoor PCB. This is done by setting S6 (on some models it is called NI_SD-AD_FD) DIP Switches to OFF-OFF-OFF positions like show on the below picture.