Difference between revisions of "CoolMasterNet FW Update"
Jump to navigation
Jump to search
Line 16: | Line 16: | ||
| 01 May 2018 | | 01 May 2018 | ||
| Fixes, MD,ME,LG Locks, FJ V1 support, FJ modes improvements, KNX VAM support, HH support | | Fixes, MD,ME,LG Locks, FJ V1 support, FJ modes improvements, KNX VAM support, HH support | ||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
| '''Stable''' | | '''Stable''' | ||
|- | |- |
Revision as of 05:42, 30 June 2018
Firmware update
- Download and Install Cool Automation SW Package:
CoolAutomation-180220_build_3.1.exe
- Get CoolMasterNet FW Image. Latest FW Image can be downloaded here:
Image | Version | Date | Key Features | Status |
---|---|---|---|---|
<htmltag tagname="a" href="http://coolautomation.com/lib/firmware/CMNET/0.6.2/CM5-0.6.2.INC" download>CM5-0.6.2.INC</htmltag> | 0.6.2 | 01 May 2018 | Fixes, MD,ME,LG Locks, FJ V1 support, FJ modes improvements, KNX VAM support, HH support | Stable |
- Connect CoolMasterNet to USB. If it is the first time connection, USB driver will be installed
- Run CoolAutomation FW Updater
- Load FW Image
- Click Update Firmware
Forced BOOT Mode
In certain situations, like for instance in case of power outage during regular FW update, CoolMasterNet can become irresponsible due to a luck of proper FW. In this case, to recover CoolMasterNet, it has to be updated via forced BOOT mode.
- Set all dip switches on R line into ON position (up). Remember previous status of R dip switches. Do not change dip switches on P,Q,S lines
- Power reset CoolMasterNet device. It will stay in forced BOOT mode.
- Run FW Update.
- After FW Update done, restore R line dip switches and power reset CoolMasterNet.
Safe Mode
Sometimes due to wrong configurations made in CoolMasterNet it can become irresponsible. In this case CoolMasterNet can be powered up in Safe Mode.
- Set all dip switches on Q line into ON position (up). Remember previous status of Q dip switches. Do not change dip switches on P,R,S lines
- Power reset CoolMasterNet device. It will stay in SAFE MODE.
- In Safe Mode CoolMasterNet can interface via RS232 or USB connection only. ETH and HVAC Lines are disabled.
- After configurations are done, restore Q line dip switches and power reset CoolMasterNet.