Difference between revisions of "Samsung"
(6 intermediate revisions by the same user not shown) | |||
Line 18: | Line 18: | ||
|- | |- | ||
| style="text-align: center; " | 103 | | style="text-align: center; " | 103 | ||
+ | | Communication Error Between Indoor Unit Panel and Main | ||
| | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 104 | ||
+ | | Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 105 | ||
+ | | Communication Error in between sensing space module and Indoor unit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 106 | ||
+ | | Communication Error Between LCD and Panel | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 107 | ||
+ | | Communication Error Between LCD Outdoor Unit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 108 | ||
+ | | Error due to repeated address setting (When 2 or more devices has same address within the network) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 109 | ||
+ | | Communication error - indoor address is not completed. Check communication wire between indoor and | ||
+ | outdoor, outdoor unit quantity, indoor address setting status. | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 121 | ||
+ | | Error of ROOM Temperature Sensor in Indoor unit short/open | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 122 | ||
+ | | Error of Evaporator_in Sensor of Indoor unit short/open | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 123 | ||
+ | | Error of Evaporator_out Sensor of Indoor unit short/open | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 124 | ||
+ | | Indoor Unit Communication Error (Indoor Unit / | ||
+ | Outdoor Unit Communication Error displayed in Outdoor unit) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 125 | ||
+ | | Eva_mid2 Sensor of Indoor unit short/open | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 127 | ||
+ | | Indoor Temperature (Suction Temperature) Sensor breakaway Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 128 | ||
+ | | Breakaway of Indoor unit Evaporator_in Sensor | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 129 | ||
+ | | Breakaway of Indoor unit Evaporator_out Sensor | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 130 | ||
+ | | Breakaway of evaporator in and evaporator out sensors in indoor unit at the same time | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 131 | ||
+ | | Sub(Electronic) Heater Sensor 1 Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 132 | ||
+ | | Sub(Electronic) Heater Sensor 2 Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 133 | ||
+ | | Sub(Electronic) Heater Sensor 3 Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 134 | ||
+ | | Shutter Sensor Error (In case of model which have two shutter, upper Error : Aurora) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 135 | ||
+ | | Perfect Fan Sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 136 | ||
+ | | Shutter Sensor Error (In case, model which have two shutter Error in bottom : Aurora) | ||
+ | | Aurora Bottom Sensor | ||
+ | |- | ||
+ | | style="text-align: center; " | 137 | ||
+ | | VOC SENSOR OPEN/SHORT ERROR | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 138 | ||
+ | | GAS SENSOR OPEN/SHORT ERROR | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 139 | ||
+ | | ERV CO2 SENSOR OPEN/SHORT ERROR | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 140 | ||
+ | | Indoor Dust sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 141 | ||
+ | | IAQ CO2 SENSOR OPEN/SHORT ERROR | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 142 | ||
+ | | Indoor Unit Humid Sensor short/open | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 143 | ||
+ | | Sensing space Sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 144 | ||
+ | | Eva2_in Sensor of Indoor Unit short/open | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 145 | ||
+ | | Eva2_out Sensor of Indoor Unit short/open | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 146 | ||
+ | | EEV Inlet Sensor short/open | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 147 | ||
+ | | Indoor Eva2_in Sensor break away Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 148 | ||
+ | | Indoor Eva2_out Sensor break away Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 149 | ||
+ | | AHU Master Indoor room sensor setting error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 150 | ||
+ | | RESERVED(DMS-SNET3 Error) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 151 | ||
+ | | Open error of electoronic expansion valve in indoor unit(2nd) | ||
+ | | Check MCU addressing if HR | ||
+ | |- | ||
+ | | style="text-align: center; " | 152 | ||
+ | | Close error of electoronic expansion valve in indoor unit(2nd) | ||
+ | | Check MCU addressing if HR | ||
+ | |- | ||
+ | | style="text-align: center; " | 153 | ||
+ | | Dectect Indoor float s/w 2nd | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 154 | ||
+ | | Indoor unit Fan Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 155 | ||
+ | | Indoor unit Fan2 Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 156 | ||
+ | | Indoor unit (EEV2) open error 2nd | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 157 | ||
+ | | Indoor unit (EEV2) close error 2nd | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 158 | ||
+ | | UDoor upper operation Error | ||
+ | | (check Photo Sensor or operating Relay Error) | ||
+ | |- | ||
+ | | style="text-align: center; " | 159 | ||
+ | | UDoor lower operation Error | ||
+ | | (check Photo Sensor or operating Relay Error) | ||
+ | |- | ||
+ | | style="text-align: center; " | 161 | ||
+ | | Cooling and Heating mixed operating Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 162 | ||
+ | | Outdoor unit EEPROM error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 163 | ||
+ | | EEPROM OPTION SETTING ERROR | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 165 | ||
+ | | Elect Discharge Temp Protect Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 166 | ||
+ | | Electric motor related to no wind Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 167 | ||
+ | | Unsing peripheral in Indoor Unit Option DIP S/W set Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 168 | ||
+ | | IAQ Safety S/W Open Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 169 | ||
+ | | AHU EEV Fault detection error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 170 | ||
+ | | Error; Fahrenheit /Celsius degree use same time (Indoor Unit which selected Celsius) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 174 | ||
+ | | ERV + heat exchanger inlet temperature sensor short / open | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 175 | ||
+ | | Outdoor built-in indoor temperature sensor short / open error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 177 | ||
+ | | In hydro box, take place emergency signal Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 180 | ||
+ | | MCU SOL Valve cooling/heating opening 1st at the same time | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 181 | ||
+ | | MCU SOL Valve cooling/heating opening 1st at the same time | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 185 | ||
+ | | Missconnect power line to Indoor Unit communication line | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 186 | ||
+ | | sMPI(SPI) Feedback Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 187 | ||
+ | | K1Filter Feedback Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 190 | ||
+ | | While in checking pipe, no change Temp in Eva_in or change Temp Eva_in of other Indoor unit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 191 | ||
+ | | While in checking pipe, no change Temp in Eva_out or change Temp Eva_out of other Indoor unit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 192 | ||
+ | | Indoor Unit COVER OPEN (Indoor unit switch for safety) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 193 | ||
+ | | Indoor Panel Zero-Crossing Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 194 | ||
+ | | Indoor Main Zero-Crossing Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 195 | ||
+ | | IAQ safety S/W Open Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 198 | ||
+ | | Error due to disconnected thermal fuse of indoor unit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 199 | ||
+ | | Error in Display Status of No pipe checking | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 201 | ||
+ | | After complete Tracking 5 times, mismatch of the indoor unit quantity set with those | ||
+ | found by ODU error (some of indoor units disconnected communication wire, IDU powered off etc.) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 202 | ||
+ | | System Down (All Indoor unit Short) due to Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 203 | ||
+ | | Outdoor Unit Communication Error Between MAIN-- SUB | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 204 | ||
+ | | After completing Tracking 5 times, there is different with a number of set MCU and communicated MCU | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 205 | ||
+ | | Communication Error on all PBA within the outdoor unit C-Box, communication cable error | ||
+ | Communication Error Between Outdoor Unit Inv Micom -- Fan Motor Micom | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 206 | ||
+ | | Communication Error Between Outdoor Unit Main PBA - Sub PBA | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 206-C001 | ||
+ | | Communication Error Between Outdoor Unit Main PBA - Sub PBA | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 206-C002 | ||
+ | | FAN PBA communication error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 206-C003 | ||
+ | | INV1 PBA communication error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 206-C004 | ||
+ | | INV2 PBA communication error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 210 | ||
+ | | Can NOT communicate with MCU over 2 min | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 211 | ||
+ | | Indoor unit connected with confluence kit without continunity | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 212 | ||
+ | | Indoor unit connected with confluence kit and setting address was overlapped more than 3 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 213 | ||
+ | | MCU address not matched with indoor unit address | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 214 | ||
+ | | MCU address not matched with outdoor unit address | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 215 | ||
+ | | Rotary switch for indoor unit address in MCU was over lapped among MCUs | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 216 | ||
+ | | DIP switch for indoor unit setting was ON position even though indoor unit was not connected | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 217 | ||
+ | | DIP switch for indoor unit setting was OFF position even though indoor unit was connected | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 218 | ||
+ | | Setting number of indoor unit in MCU is larger than installed indoor units | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 219 | ||
+ | | Error on temperature sensor located on MCU intercooler inlet (Short or Open) | ||
+ | MCU Over Cooling In Sensor Open/Short | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 220 | ||
+ | | Error on temperature sensor located on MCU intercooler outlet (Short or Open) | ||
+ | MCU Over Cooling Out Sensor Open/Short | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 221 | ||
+ | | OUT temperature SENSOR ERROR (OPEN/SHORT) | ||
+ | - ERROR LEVEL: more than 4.9V(-50oC), less than 0.4V(93oC) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 226 | ||
+ | | OUT_temperature temperature Sensor breakaway Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 231 | ||
+ | | COND_OUT Main temperature SENSOR ERROR (OPEN/SHORT) | ||
+ | - ERROR LEVEL: More than 4.9V(-50oC), less than 0.4V(93oC)” | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 236 | ||
+ | | COND_OUT Sub1 temperature SENSOR ERROR (OPEN/SHORT) | ||
+ | - ERROR LEVEL: More than 4.9V(-50oC), less 0.4V(93oC)” | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 237 | ||
+ | | COND temperature SENSOR ERROR (OPEN/SHORT) | ||
+ | - ERROR LEVEL: More than 4.9V(-50oC), less than 0.4V(93oC) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 241 | ||
+ | | COND_MID or COND OUT Sensor of Outdoor Unit breakaway Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 242 | ||
+ | | Outdoor Unit Heater Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 246 | ||
+ | | COND_OUT 1 breakaway | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 251 | ||
+ | | PWM DISCHARGE temperature SENSOR ERROR (OPEN/SHORT) | ||
+ | - ERROR detect Condition: detect Outdoor temperature more than -10oC | ||
+ | - ERROR LEVEL: More than 4.95V(-30’C), less than 0.5V(151’C) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 256 | ||
+ | | Fixed COMP 1 DCHRG SENSOR ERROR (OPEN/SHORT) | ||
+ | - ERROR detect Condition: detect Outdoor temperature more than | ||
+ | - ERROR LEVEL: More than 4.95V(-30’C), less than 0.5V(151’C) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 257 | ||
+ | | Fixed COMP 2 DCHRG SENSOR ERROR (OPEN/SHORT) | ||
+ | - ERROR detect Condition: detect Outdoor temperature more than -10oC | ||
+ | - ERROR LEVEL: more than 4.95V(-30’C),less than 0.5V(151’C)” | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 258 | ||
+ | | Fixed COMP 3 DCHRG SENSOR ERROR (OPEN/SHORT) | ||
+ | - ERROR detect Condition: Outdoor temperature more than -10 detect oC | ||
+ | - ERROR LEVEL: more than 4.95V(-30’C),less than 0.5V(151’C) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 261 | ||
+ | | Digital COMP_discharge Sensor breakaway Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 262 | ||
+ | | Fixd COMP1_discharge Sensor breakaway Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 263 | ||
+ | | Fixd COMP2_discharge Sensor breakaway Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 264 | ||
+ | | Fixd COMP3_discharge Sensor breakaway Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 265 | ||
+ | | SUMP temperature sensor breakaway (Main) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 266 | ||
+ | | SUMP temperature sensor breakaway (Sub1) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 267 | ||
+ | | High Pressure SENSOR breakaway ERROR | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 268 | ||
+ | | SUMP temperature sensor breakaway (Sub3) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 269 | ||
+ | | SUCTION Sensor breakaway | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 271 | ||
+ | | Digital COMP Sump_temperature Digital SENSOR ERROR (OPEN/SHORT) | ||
+ | - ERROR detect Condition: detect outdoor temperature -10oC | ||
+ | - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 276 | ||
+ | | FIXED COMP1 Sump_temperature SENSOR ERROR (OPEN/SHORT) | ||
+ | - ERROR detect Condition: detect outdoor temperature more than -10oC | ||
+ | - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 277 | ||
+ | | FIXED COMP2 Sump_temperature SENSOR ERROR (OPEN/SHORT) | ||
+ | - ERROR detect Condition: detect outdoor temperature -10oC | ||
+ | - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 278 | ||
+ | | FIXED COMP3 Sump_temperature FIXED 3 SENSOR ERROR (OPEN/SHORT) | ||
+ | - ERROR detect Condition: detect outdoor temperature more than -10oC | ||
+ | - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 291 | ||
+ | | High pressure SENSOR ERROR (OPEN/SHORT) while in operating COMP only, detect | ||
+ | (shortError: less than 0.4v, Error detect), (OPENError: over 4.2v, Error detect) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 296 | ||
+ | | Low Pressure SENSOR ERROR (OPEN/SHORT) while in operating COMP only, detect | ||
+ | (shortError: less than 0.4v, Error detect), (OPENError:over 4.7v, Error detect) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 301 | ||
+ | | High Pressure SENSOR breakaway ERROR | ||
+ | | | ||
+ | |- | ||
+ | |||
+ | | style="text-align: center; " | 306 | ||
+ | | Low Pressure SENSOR breakaway ERROR | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 307 | ||
+ | | Oil Balance Sensor SHORT/OPEN | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 308 | ||
+ | | SUCTION Sensor SHORT/OPEN | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 309 | ||
+ | | Oil Balace Sensor2 Sensor SHORT/OPEN | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 310 | ||
+ | | Oil Balance Sensor3 Sensor SHORT/OPEN | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 311 | ||
+ | | Double pipe Sensor SHORT/OPEN | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 312 | ||
+ | | Main Cooling Sol Valve Open Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 313 | ||
+ | | 4-Way Valve operation Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 314 | ||
+ | | Oil Balace Sensor4 SHORT/OPEN | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 315 | ||
+ | | CT1 Sensor Short or Open | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 316 | ||
+ | | CT2 Sensor Short or Open | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 317 | ||
+ | | CT3 Sensor Short or Open | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 320 | ||
+ | | OLP Sensor SHORT / OPEN | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 321 | ||
+ | | EVI INLET Sensor SHORT/OPEN | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 322 | ||
+ | | EVI OUTLET Sensor SHORT/OPEN | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 323 | ||
+ | | Error on suction sensor 2 (Short or Open) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 324 | ||
+ | | Outdoor Unit Fan Motor Current Sensor SHORT / OPEN | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 325 | ||
+ | | Outdoor Unit Fan2 Motor Current Sensor SHORT / OPEN | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 330 | ||
+ | | Outdoor plumbing inlet sensor out 0 time (TA_0) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 331 | ||
+ | | Outdoor sensor out once the entrance pipe (TA_1) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 332 | ||
+ | | 2, the inlet pipe outdoor sensor out (TA_2) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 333 | ||
+ | | Three times the inlet pipe outdoor sensor out (TA_3) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 334 | ||
+ | | Outdoor four times the inlet pipe sensor out (TA_4) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 335 | ||
+ | | Outdoor pipe exit sensor out 0 time (TB_0) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 336 | ||
+ | | 1 outdoor sensor out pipe outlet (TB_1) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 337 | ||
+ | | Outdoor sensor out two times pipe outlet (TB_2) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 338 | ||
+ | | Outdoor sensor out three times pipe outlet (TB_3) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 339 | ||
+ | | Outdoor sensor out four pipe outlet (TB_4) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 346 | ||
+ | | Error due to operation failure of Fan2 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 347 | ||
+ | | Motor wire of Fan2 is not connected | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 348 | ||
+ | | Lock error on Fan2 of outdoor unit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 353 | ||
+ | | Error due to overheated motor of outdoor unit’s Fan2 | ||
| | | | ||
|- | |- | ||
− | | style="text-align: center; " | | + | | style="text-align: center; " | 355 |
+ | | Error due to overheated IPM of Fan2 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 361 | ||
+ | | 2 CT1 inverter compressor start failure, or a low-current | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 364 | ||
+ | | Error due to over-current of inverter compressor 2. 2 DC Peak Inverter compressor stop | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 365 | ||
+ | | V-limit error of inverter compressor 2. 2 inverter compressor overload stops (30A or more) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 366 | ||
+ | | Error due to over voltage /low voltage of inverter PBA2. Less than 2 DC Link Voltage 150V 410V inverter over | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 367 | ||
+ | | Error due to unconnected wire of compressor 2. Inverter compressor rotation over 2 Wire dependence or compressor | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 368 | ||
+ | | Output current sensor error of inverter PBA2. 2 Comp inverter current sensor error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 369 | ||
+ | | DC voltage sensor error of inverter PBA2. 2 DC Link Inverter Sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 371 | ||
+ | | 2 inverter outdoor unit EEPROM Read / Write error (OTP error) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 374 | ||
+ | | Heat sink temperature sensor error of inverter PBA2. 2 inverter heat sink temperature sensor error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 378 | ||
+ | | Hall IC connection error of Fan2. Outdoor fan 2 IPM H / W OC | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 385 | ||
+ | | Error due to input current of inverter 2. 2 inverter input current sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 386 | ||
+ | | Over-voltage/low-voltage error of Fan2 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 387 | ||
+ | | Outdoor fan 2 Hall Sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 389 | ||
+ | | V-limit error on Fan2 of compressor | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 391 | ||
+ | | Fan Controller 2 EEPROM Read / Write Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 393 | ||
+ | | Output current sensor error of Fan2. Fan Controller 2 Current sensor error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 396 | ||
+ | | DC voltage sensor error of Fan2. Fan Controller 2 DC Link sensor error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 399 | ||
+ | | Heat sink temperature sensor error of Fan2. 2 fan controller heat sink temperature sensor error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 400 | ||
+ | | Error due to overheat caused by contact failure on IPM of Inverter PBA2 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 401 | ||
+ | | Outdoor Freezing detect 1 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 402 | ||
+ | | Outdoor Freezing detect 2 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 403 | ||
+ | | Outdoor Freezing detect 3 - Freeze COMP DOWN | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 404 | ||
+ | | Outdoor overload 1 Protection Control Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 405 | ||
+ | | Outdoor overload 2 Protection Control Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 406 | ||
+ | | Outdoor overload 3 Protection Control Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 407 | ||
+ | | COMP down due to High PressureSensor Protection Control 1 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 408 | ||
+ | | COMP down due to High PressureSensor Protection Control 2 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 409 | ||
+ | | COMP down due to High PressureSensor Protection Control 3 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 410 | ||
+ | | COMP down due to Low PressureSensor Protection Control 1 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 411 | ||
+ | | COMP down due to Low PressureSensor Protection Control 2 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 412 | ||
+ | | COMP down due to Low PressureSensor Protection Control 3 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 413 | ||
+ | | Outdoor SUMP DOWN_1 Protection Control | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 414 | ||
+ | | Outdoor SUMP DOWN_2 Protection Control | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 415 | ||
+ | | Outdoor SUMP DOWN_3 Protection Control | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 416 | ||
+ | | Outdoor DischargeTemperature_1 Protection Control | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 417 | ||
+ | | Outdoor DischargeTemperature_2 Protection Control | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 418 | ||
+ | | Outdoor DischargeTemperature_3 Protection Control | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 419 | ||
+ | | Outdoor EEV#1 opening 6th Self-Check Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 420 | ||
+ | | Outdoor EEV#2 opening 6th Self-Check Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 421 | ||
+ | | Outdoor EEV#3 opening 6th Self-Check Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 422 | ||
+ | | Outdoor EEV#1 closing 6th Self-Check Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 423 | ||
+ | | Outdoor EEV#2 closing 6th Self-Check Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 424 | ||
+ | | Outdoor EEV#3 closing 6th Self-Check Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 425 | ||
+ | | Outdoor Reverse Phase or Missing Phase detect 1 Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 426 | ||
+ | | Outdoor Reverse Phase or Missing Phase detect 2 Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 427 | ||
+ | | Outdoor Reverse Phase or Missing Phase detect 3 Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 428 | ||
+ | | COMP down by Compression Ratio control Error 1 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 429 | ||
+ | | COMP down by Compression Ratio control Error 2 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 430 | ||
+ | | COMP down by Compression Ratio control Error 3 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 431 | ||
+ | | Oil Balance Valve1 Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 432 | ||
+ | | Oil Balance Valve2 Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 433 | ||
+ | | Oil Balance Valve3 Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 434 | ||
+ | | Oil Balance Valve opening Error (In DVM PLUS 2, HotGasValve Opening Error) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 435 | ||
+ | | Water Cooling Flow Switch Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 436 | ||
+ | | Evaporator Protect for Freeze and Burst Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 437 | ||
+ | | Oil Balance Valve Closing Error(In DVM PLUS 2, HotGasValve Opening Error) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 438 | ||
+ | | EVI EEV Opening Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 439 | ||
+ | | Error due to refrigerant leakage | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 440 | ||
+ | | Forbid Heat mode operation when outdoor temperature is over 30oC | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 441 | ||
+ | | Forbid Cooling Mode when OutdoorTemperature ia less than -5oC | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 442 | ||
+ | | Forbid an operation during heat mode with refrigerant charging operation when out door temperature | ||
+ | is over 15oC | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 443 | ||
+ | | Before Cooling working, less than Low Pressure 1K(inability to re-operate) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 445 | ||
+ | | CCH is detached. CCH Self-Check Error (CCH malfunction Or Sump Sensor miss connection) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 446 | ||
+ | | Error due to operation failure of Fan1. Fan Controller 1 Fan failed maneuver | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 447 | ||
+ | | Motor wire of Fan1 is not connected. Fan controller wiring 1 Wire U.S. | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 448 | ||
+ | | Lock error on Fan1. Fan Controller 1 Lock error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 450 | ||
+ | | COND High Temperature(Protection Control) Every Time | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 451 | ||
+ | | Low Pressure Switch Low Pressure(Protection Control) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 452 | ||
+ | | Instant power off Error (delete when COMP re-operate) | ||
+ | Outdoor Zero-Crossing Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 453 | ||
+ | | Outdoor Fan high temperaturet Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 454 | ||
+ | | OutdoorFan RPM Error (more than 2500rpm and the difference that target velocity compare with practical | ||
+ | velocity is more than 100rpm per 10SEC, more than 10 times) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 455 | ||
+ | | OutdoorFan IPM(Internal PCB Module) high temperature Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 456 | ||
+ | | OutdoorFan Overcurrent Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 457 | ||
+ | | OutdoorFan Reversed direction of the wind Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 458 | ||
+ | | Outdoor unit Fan (Fan Error) Or CT1 over currency | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 459 | ||
+ | | Outdoor unit IPM Fault Error Or CT2 over currency | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 460 | ||
+ | | Outdoor unit communication-power disconnected detect Or CT3 over currency | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 461 | ||
+ | | Inverter COMP operating failure Or CT1 low currency | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 462 | ||
+ | | All currency control COMP Stop Or CT2 low currency | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 463 | ||
+ | | OLP Temperature control COMP Stop Or CT3 low currency | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 464 | ||
+ | | DC Peak COMP stop | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 465 | ||
+ | | COMP Overload stop(over 30A) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 466 | ||
+ | | DC Link voltage less than 150V, over 410V | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 467 | ||
+ | | COMP revolute error Or COMP Wire In-connection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 468 | ||
+ | | Inv Comp Current Sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 469 | ||
+ | | DC Link Sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 470 | ||
+ | | Outdoor unit EEPROM Read/Write Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 471 | ||
+ | | Outdoor unit EEPROM Read/Write Error(OTP error) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 472 | ||
+ | | Outdoor unit Zero crossing Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 473 | ||
+ | | Inverter Comp Lock Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 474 | ||
+ | | Heat sink temperature sensor error of inverter PBA1 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 475 | ||
+ | | Outdoor unit BLDC Fan 2 Error Or | ||
+ | OutdoorFan2 RPM Error (more than 2500rpm and the difference that target velocity compare with practical | ||
+ | velocity is more than 100rpm per 10SEC, more than 10 times) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 476 | ||
+ | | 4wAY Error detect | ||
+ | | Self-Check, After 6 times, COMP DOWN | ||
+ | |- | ||
+ | | style="text-align: center; " | 477 | ||
+ | | Control for protecting liquid refrigerant | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 478 | ||
+ | | Error due to over current of Fan1. OutdoorFan IPM H/W OC | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 479 | ||
+ | | 4WAY miss connection detect Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 480 | ||
+ | | Fixed Comp 1 Stege OLP Protection Control(leakage for refrigerant Error) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 481 | ||
+ | | Comp1 operating Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 482 | ||
+ | | Comp2 operating Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 483 | ||
+ | | Overvoltage of H/W Detect DC Link | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 484 | ||
+ | | PFC Overload (overcurrent) Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 485 | ||
+ | | Error due to input current of inverter 1. Input current Sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 486 | ||
+ | | Error due to over voltage/low voltage of Fan. Outdoor Fan DC-Link Voltage Under/Over Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 487 | ||
+ | | Hall IC error of Fan1. Outdoor Fan Hall Sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 489 | ||
+ | | V-limit error on Fan1 of compressor | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 490 | ||
+ | | Outdoor Temperature 0 degrees & Indoor Temperature less than 0 degrees prohibition to operate | ||
+ | | ERV Ventilation System | ||
+ | |- | ||
+ | | style="text-align: center; " | 491 | ||
+ | | Fan Controller1 EEPROM Read/Write Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 492 | ||
+ | | Outdoor Fan2 IPM H/W OC | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 493 | ||
+ | | Output current sensor error of Fan1. Fan Controller1 Current Sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 494 | ||
+ | | Delayed time Error due to OutdoorFan2 Fan Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 495 | ||
+ | | Outdoor Fan2 Overheat Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 496 | ||
+ | | DC voltage sensor error of Fan1. Fan Controller1 DC Link Sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 497 | ||
+ | | Outdoor Fan2 Overcurrent Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 498 | ||
+ | | Outdoor Fan2 IPM(Internal PCB Module) Overheat Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 499 | ||
+ | | Heat sink temperature sensor error of Fan1. Fan Controller1 Heat Sink Temp Sensor Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 500 | ||
+ | | IPM Overheat Error for Inverter COMP | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 503 | ||
+ | | Error due to alert the user to check if the service valve is closed | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 504 | ||
+ | | Error due to self diagnosis of compressor operation | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 505 | ||
+ | | Error due to self diagnosis of high pressure sensor | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 506 | ||
+ | | Error due to self diagnosis of low pressure sensor | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 512 | ||
+ | | RESERVED(DMS-SNET3 Error) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 551 | ||
+ | | Defrost working | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 552 | ||
+ | | Low Discharge Pressure | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 553 | ||
+ | | Equability operation | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 554 | ||
+ | | loading_failure / total Leakage of Refrigerant of Outdoor Unit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 555 | ||
+ | | Recovery of oil | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 556 | ||
+ | | Outdoor Unit power set option Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 557 | ||
+ | | When DPM mode, Product option are not same between indoor units | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 559 | ||
+ | | Indoor Unit operating stop due to detect unknown error in Outdoor Unit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 560 | ||
+ | | Outdoor Unit Switch option setting error(not applied) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 561 | ||
+ | | Outdoor Unit SA(SUPPLY AIR) FAN RPM | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 562 | ||
+ | | Outdoor Unit RA(ROOM AIR) FAN RPM | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 563 | ||
+ | | Indoor Unit mixed install error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 564 | ||
+ | | IAQ Clean Fan Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 565 | ||
+ | | Miss connection Error between Comp and power wire - power line of Eva1 connect with Comp2 or | ||
+ | power line of Eva2 connect with Comp1 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 570 | ||
+ | | Boot Code Check FAIL | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 573 | ||
+ | | Error due to using single type outdoor unit in a module installation | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 574 | ||
+ | | Total Leakage of Refrigerant of Outdoor Unit 2 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 575 | ||
+ | | Total Leakage of Refrigerant of Outdoor Unit 3 (Comp1, Comp2 bot detected) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 601 | ||
+ | | Wired LCD (controller) <-> Indoor Unit Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 602 | ||
+ | | Master Wire LCD <-> Slave Wire LCD Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 603 | ||
+ | | Communication Packet Error (Baudrate / different communication type) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 604 | ||
+ | | Wired LCD (controller) <-> Indoor Unit Tracking Error over 10 times | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 605 | ||
+ | | 7 Day Scheduler <-> Wire LCD ,CAUR Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 606 | ||
+ | | Wire LCD COM1/COM2 Cross Install Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 607 | ||
+ | | Wile Wire LCD Master-Master installation, Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 608 | ||
+ | | External linkage ERV Controller No installation Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 609 | ||
+ | | External linkage Indoor No installation Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 610 | ||
+ | | CAUR <-> Transmitter Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 611 | ||
+ | | DMS <-> CAUR Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 612 | ||
+ | | DMS <-> PEAK Transmitter Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 613 | ||
+ | | DMS <-> PIM/SIM Transmitter Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 614 | ||
+ | | Amount of electricity system <-> PIM/SIM Transmitter Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 615 | ||
+ | | Transmitter <-> Indoor unit Communication Error (After complete Transmitter Tracking, for 2min some indoor | ||
+ | unit can’t communicate.) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 616 | ||
+ | | Transmitter <-> Outdoor unit Communication Error (After completeTransmitter Tracking, for 2min outdoor | ||
+ | unit can’t communicate) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 617 | ||
+ | | Peak power Transmitter <-> Demand Controller Communication Error, Demand Transmitter | ||
+ | <-> Amount of eletricity system communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 618 | ||
+ | | ERV Controller+indoor unit (16EA) over Max install number Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 619 | ||
+ | | Celcius/Fahrenheit indoor unit mixed install error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 620 | ||
+ | | New wired remote controller "Celcius/Fahrenheit" set error (DIP S/W #4 set error) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 621 | ||
+ | | New Wire Remote controller Master/Slave Dip Switch option Set Error (Difference with set option of | ||
+ | Master and Slave) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 622 | ||
+ | | Demand Controller / select the type of amount of electricity system Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 623 | ||
+ | | Demand Transmitter PT / CT ratio set Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 624 | ||
+ | | Demand Transmitter data receive error from amount of electricity | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 625 | ||
+ | | Master DMS ? Slave DMS Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 626 | ||
+ | | ERV linkage wire remote controller(AWR-WE00) ERV separate installation Error (not connect indoor unit | ||
+ | and, only ERV be installed) indoor unit linkage wire remocontroller(AWR-VH10) indoor unit separate | ||
+ | installation Error (not connect indoor unit and, only ERV be installed) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 627 | ||
+ | | While in linkage controll Master/Slave Wire Remote controller, Slave Wire Remote controller 2EA installation | ||
+ | Error (Installing Wire Remocontroller set slave in Master Wire Remocontroller 2EA at the same time) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 628 | ||
+ | | DMS <-> Transmitter Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 629 | ||
+ | | DMS <-> DDC Communication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 630 | ||
+ | | ERV wire remote controller normal ventilation option set Error | ||
+ | - Check normal ventilation option set only. | ||
+ | - ERV normal ventilation No option, use Wire Remote controller option normal ventilation | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 631 | ||
+ | | ERVWire Remote controller auto ventilation option set Error | ||
+ | - Check set auto ventilation only | ||
+ | - ERV auto ventilation no option, use wire remote controller auto ventilation | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 632 | ||
+ | | Error when input the pulse except set the value of Pulse Width by PIM | ||
+ | 1. less than 20ms , 2. over 400ms , 3. over range of set pulse width, 4. repeated purse over 3min | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 652 | ||
+ | | While COM 1 Dual Master installation Commnunication Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 653 | ||
+ | | Temperature Sensor Open/Short Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 654 | ||
+ | | FRAM Error or damper Error(ERV model) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 655 | ||
+ | | RESERVED(DMS-SNET3 Error) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 656 | ||
+ | | RESERVED(DMS-SNET3 Error) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 701 | ||
+ | | Float 1st | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 702 | ||
+ | | Indoor EEV clsosing 1st | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 703 | ||
+ | | Indoor EEV opening 1st | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 720 | ||
+ | | Outdoor EEV#1 opening Self-Check Every time error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 721 | ||
+ | | Outdoor EEV#2 opening Self-Check Every time error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 722 | ||
+ | | Outdoor EEV#3 opening Self-Check Every time error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 723 | ||
+ | | Outdoor EEV#1 closing Self-Check Every time error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 724 | ||
+ | | Outdoor EEV#2 closing Self-Check Every time error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 725 | ||
+ | | Outdoor EEV#3 closing Self-Check Every time error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 768 | ||
+ | | RESERVED(DMS-SNET3) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 801 | ||
+ | | [GHP-R410A] communication error : “IF <-> Outdoor unit” : Disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 802 | ||
+ | | [GHP-R410A] communication error : “Outdoor unit <-> IF” : Disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 803 | ||
+ | | [GHP-R410A] communication error : “IF <-> Indoor unit” some disconnect in Indoor unit (communicating) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 804 | ||
+ | | [GHP-R410A] communication error : Among outdoor unit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 805 | ||
+ | | [GHP-R410A] Error setting outdoor unit organization | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 806 | ||
+ | | [GHP-R410A] Remocon Sensor disconnect/short circuit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 807 | ||
+ | | [GHP-R410A] outdoor liquid pipe Sensor disconnect/short circuit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 808 | ||
+ | | [GHP-R410A] outdoor Unit - overcooling heat exchanger entry temp thermystor disconnect/short circuit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 809 | ||
+ | | [GHP-R410A]COMP suction temp overheat | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 810 | ||
+ | | [GHP-R410A] COMP suction superheat not soar | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 811 | ||
+ | | [GHP-R410A] refrigerant high pressure Switch disconnect | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 812 | ||
+ | | [GHP-R410A] Gas EEV Output error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 813 | ||
+ | | [GHP-R410A] refrigerant low pressure Sensor error(2nd) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 814 | ||
+ | | [GHP-R410A] refrigerant high pressure Sensor error 1 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 815 | ||
+ | | [GHP-R410A] refrigerant high pressure Sensor error 2 (value of high pressure sensor less | ||
+ | than standard low pressure) | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 816 | ||
+ | | [GHP-R410A] Water Pump operation failure | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 817 | ||
+ | | [GHP-R410A] Water Pump a number of revolute error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 818 | ||
+ | | [GHP-R410A] IPM(outdoor unit FAN operating Driver) error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 819 | ||
+ | | [GHP-R410A] outdoor heat exchange Fan 1 operating failure | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 820 | ||
+ | | [GHP-R410A] outdoor heat exchange Fan 2 operating failure | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 821 | ||
+ | | [GHP-R410A] outdoor heat exchange Fan 3 operating failure | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 822 | ||
+ | | [GHP-R410A] outdoor heat exchange Fan 1 a number of revolute error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 823 | ||
+ | | [GHP-R410A] outdoor heat exchange Fan 2 a number of revolute error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 824 | ||
+ | | [GHP-R410A] outdoor heat exchange Fan 3 a number of revolute error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 825 | ||
+ | | [GHP-R410A] outdoor Unit - heat exchange Fan error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 826 | ||
+ | | [GHP-R410A] outdoor Unit - Accum exit temp thermystor 1 disconnect/short circuit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 827 | ||
+ | | [GHP-R410A] outdoor Unit - Accum exit temp thermystor 2 disconnect/short circuit | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 828 | ||
+ | | [GHP-R410A] outdoor unit Unit - refrigerant low pressure Switch disconnect | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 829 | ||
+ | | [GHP-R410A] refrigerant low pressure error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 830 | ||
+ | | [GHP-R410A] three phase error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 831 | ||
+ | | [GHP-R410A] one phase power part error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 832 | ||
+ | | [GHP-R410A] Main - Sub MICOM Program Version Unmatch | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 833 | ||
+ | | [GHP-R410A] indoor unit connection number Over | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 834 | ||
+ | | [GHP-R410A] indoor unit connection capacity Over | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 835 | ||
+ | | [GHP-R410A] outdoor-indoor connection Unmatch | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 836 | ||
+ | | [GHP-R410A] Outdoor Unit -Regular Inspection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 837 | ||
+ | | [GHP-R410A] Refrigerant High pressure error 1 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 838 | ||
+ | | [GHP-R410A] Refrigerant High pressure error 2 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 841 | ||
+ | | [GHP-R410A] Outdoor Unit Gas Temp Thermistor short/disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 843 | ||
+ | | [GHP-R410A] Engine water temp Sensor short/disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 844 | ||
+ | | [GHP-R410A] Engine discharge temp Sensor disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 845 | ||
+ | | [GHP-R410A] Engine fluid pressure error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 846 | ||
+ | | [GHP-R410A] Engine Fluid pressure Switch disconnected | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 847 | ||
+ | | [GHP-R410A] Engine over revolute 1 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 848 | ||
+ | | [GHP-R410A] Engine over revolute 2 | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 849 | ||
+ | | [GHP-R410A] Starter Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 850 | ||
+ | | [GHP-R410A] Engine a number of revolute control error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 851 | ||
+ | | [GHP-R410A] Engine Stop | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 852 | ||
+ | | [GHP-R410A] IGUNAITA(firer) low voltage | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 853 | ||
+ | | [GHP-R410A] IGUNAITA(firer) disconnect | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 854 | ||
+ | | [GHP-R410A] IGUNAITA(firer) over voltage | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 855 | ||
+ | | [GHP-R410A] Engine discharge temp Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 856 | ||
+ | | [GHP-R410A] Engine water temp overheat | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 857 | ||
+ | | [GHP-R410A] Engine operation failure | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 858 | ||
+ | | [GHP-R410A] Engine cooling | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 859 | ||
+ | | [GHP-R410A] Engine insufficient operating revolute | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 860 | ||
+ | | [GHP-R410A] Engine a number of revolute Haunting Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 861 | ||
+ | | [GHP-R410A] COMP discharge temperature overheat | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 862 | ||
+ | | [GHP-R410A] Compressor Discharge temperature Sensor1 short/disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 863 | ||
+ | | [GHP-R410A] Compressor Discharge temperature Sensor2 short/disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 864 | ||
+ | | [GHP-R410A] Compressor Discharge temperature Sensor3 short/disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 865 | ||
+ | | [GHP-R410A] Compressor Discharge temperature Sensor4 short/disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 866 | ||
+ | | [GHP-R410A] Compressor nhale temperature Sensor1 short/disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 867 | ||
+ | | [GHP-R410A] Compressor suction temperature Sensor2 short/disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 868 | ||
+ | | [GHP-R22] Outdoor Unit - Accum Entrance Temperature Sensor short/disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 869 | ||
+ | | [GHP-R22] Outdoor Unit - refrigerants Gas pipe temperature Sensor short/disconnection | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 870 | ||
+ | | [GHP-R22] Outdoor Unit - comp lubricating oil insufficiency error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 871 | ||
+ | | [GHP-R22] Outdoor Unit - Refrigerant overfill error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 872 | ||
+ | | [GHP-R22] Outdoor Unit - Compressor induction temperature error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 873 | ||
+ | | [GHP-R22] Engine cooling system Error | ||
+ | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 874 | ||
+ | | [GHP-R22] Engine Oil System error | ||
| | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 875 | ||
+ | | [GHP-R22] Engine power system Error | ||
| | | | ||
|- | |- | ||
− | | style="text-align: center; " | | + | | style="text-align: center; " | 876 |
+ | | [GHP-R22] Engine operating/control system Error | ||
| | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 880 | ||
+ | | [GHP-R410A] Outdoor Unit - Engine Temp of Cooling water low | ||
| | | | ||
|- | |- | ||
− | | style="text-align: center; " | | + | | style="text-align: center; " | 881 |
+ | | [GHP-R410A] Outdoor Unit - leakage of Engine oil | ||
| | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 882 | ||
+ | | [GHP-R410A] Outdoor Unit - Lack of Comp oil | ||
| | | | ||
|- | |- | ||
− | | style="text-align: center; " | | + | | style="text-align: center; " | 883 |
+ | | [GHP-R410A] Outdoor Unit - starter Trans voltage short | ||
| | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 901 | ||
+ | | Water Inlet Sensor(Tw1) SHORT / OPEN | ||
| | | | ||
|- | |- | ||
− | | style="text-align: center; " | | + | | style="text-align: center; " | 902 |
+ | | Water Outlet Sensor(Tw3) SHORT / OPEN | ||
| | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 903 | ||
+ | | PHE Sensor(Tw2) SHORT / OPEN | ||
| | | | ||
|- | |- | ||
− | | style="text-align: center; " | | + | | style="text-align: center; " | 904 |
+ | | Water TANK Sensor SHORT / OPEN | ||
| | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 905 | ||
+ | | SOLAR Sensor SHORT / OPEN | ||
| | | | ||
|- | |- | ||
− | | style="text-align: center; " | | + | | style="text-align: center; " | 911 |
+ | | Flow Swtich Open Error | ||
| | | | ||
+ | |- | ||
+ | | style="text-align: center; " | 912 | ||
+ | | Flow Swtich Close Error | ||
| | | | ||
|- | |- |
Latest revision as of 02:04, 19 May 2019
Connection Diagrams
Samsung Self-diagnostic Malfunction (Error) Codes
Malfunction Code |
Content of Abnormality | Notes |
---|---|---|
101 | DVM,DPM,DVS:Outdoor Unit Communication Error (Indoor unit can’t receive communication) SINGLE: Indoor Unit Panel - Main communication error |
|
102 | Outdoor Unit to Indoor Unit communication error | |
103 | Communication Error Between Indoor Unit Panel and Main | |
104 | Communication Error | |
105 | Communication Error in between sensing space module and Indoor unit | |
106 | Communication Error Between LCD and Panel | |
107 | Communication Error Between LCD Outdoor Unit | |
108 | Error due to repeated address setting (When 2 or more devices has same address within the network) | |
109 | Communication error - indoor address is not completed. Check communication wire between indoor and
outdoor, outdoor unit quantity, indoor address setting status. |
|
121 | Error of ROOM Temperature Sensor in Indoor unit short/open | |
122 | Error of Evaporator_in Sensor of Indoor unit short/open | |
123 | Error of Evaporator_out Sensor of Indoor unit short/open | |
124 | Indoor Unit Communication Error (Indoor Unit /
Outdoor Unit Communication Error displayed in Outdoor unit) |
|
125 | Eva_mid2 Sensor of Indoor unit short/open | |
127 | Indoor Temperature (Suction Temperature) Sensor breakaway Error | |
128 | Breakaway of Indoor unit Evaporator_in Sensor | |
129 | Breakaway of Indoor unit Evaporator_out Sensor | |
130 | Breakaway of evaporator in and evaporator out sensors in indoor unit at the same time | |
131 | Sub(Electronic) Heater Sensor 1 Error | |
132 | Sub(Electronic) Heater Sensor 2 Error | |
133 | Sub(Electronic) Heater Sensor 3 Error | |
134 | Shutter Sensor Error (In case of model which have two shutter, upper Error : Aurora) | |
135 | Perfect Fan Sensor Error | |
136 | Shutter Sensor Error (In case, model which have two shutter Error in bottom : Aurora) | Aurora Bottom Sensor |
137 | VOC SENSOR OPEN/SHORT ERROR | |
138 | GAS SENSOR OPEN/SHORT ERROR | |
139 | ERV CO2 SENSOR OPEN/SHORT ERROR | |
140 | Indoor Dust sensor Error | |
141 | IAQ CO2 SENSOR OPEN/SHORT ERROR | |
142 | Indoor Unit Humid Sensor short/open | |
143 | Sensing space Sensor Error | |
144 | Eva2_in Sensor of Indoor Unit short/open | |
145 | Eva2_out Sensor of Indoor Unit short/open | |
146 | EEV Inlet Sensor short/open | |
147 | Indoor Eva2_in Sensor break away Error | |
148 | Indoor Eva2_out Sensor break away Error | |
149 | AHU Master Indoor room sensor setting error | |
150 | RESERVED(DMS-SNET3 Error) | |
151 | Open error of electoronic expansion valve in indoor unit(2nd) | Check MCU addressing if HR |
152 | Close error of electoronic expansion valve in indoor unit(2nd) | Check MCU addressing if HR |
153 | Dectect Indoor float s/w 2nd | |
154 | Indoor unit Fan Error | |
155 | Indoor unit Fan2 Error | |
156 | Indoor unit (EEV2) open error 2nd | |
157 | Indoor unit (EEV2) close error 2nd | |
158 | UDoor upper operation Error | (check Photo Sensor or operating Relay Error) |
159 | UDoor lower operation Error | (check Photo Sensor or operating Relay Error) |
161 | Cooling and Heating mixed operating Error | |
162 | Outdoor unit EEPROM error | |
163 | EEPROM OPTION SETTING ERROR | |
165 | Elect Discharge Temp Protect Error | |
166 | Electric motor related to no wind Error | |
167 | Unsing peripheral in Indoor Unit Option DIP S/W set Error | |
168 | IAQ Safety S/W Open Error | |
169 | AHU EEV Fault detection error | |
170 | Error; Fahrenheit /Celsius degree use same time (Indoor Unit which selected Celsius) | |
174 | ERV + heat exchanger inlet temperature sensor short / open | |
175 | Outdoor built-in indoor temperature sensor short / open error | |
177 | In hydro box, take place emergency signal Error | |
180 | MCU SOL Valve cooling/heating opening 1st at the same time | |
181 | MCU SOL Valve cooling/heating opening 1st at the same time | |
185 | Missconnect power line to Indoor Unit communication line | |
186 | sMPI(SPI) Feedback Error | |
187 | K1Filter Feedback Error | |
190 | While in checking pipe, no change Temp in Eva_in or change Temp Eva_in of other Indoor unit | |
191 | While in checking pipe, no change Temp in Eva_out or change Temp Eva_out of other Indoor unit | |
192 | Indoor Unit COVER OPEN (Indoor unit switch for safety) | |
193 | Indoor Panel Zero-Crossing Error | |
194 | Indoor Main Zero-Crossing Error | |
195 | IAQ safety S/W Open Error | |
198 | Error due to disconnected thermal fuse of indoor unit | |
199 | Error in Display Status of No pipe checking | |
201 | After complete Tracking 5 times, mismatch of the indoor unit quantity set with those
found by ODU error (some of indoor units disconnected communication wire, IDU powered off etc.) |
|
202 | System Down (All Indoor unit Short) due to Communication Error | |
203 | Outdoor Unit Communication Error Between MAIN-- SUB | |
204 | After completing Tracking 5 times, there is different with a number of set MCU and communicated MCU | |
205 | Communication Error on all PBA within the outdoor unit C-Box, communication cable error
Communication Error Between Outdoor Unit Inv Micom -- Fan Motor Micom |
|
206 | Communication Error Between Outdoor Unit Main PBA - Sub PBA | |
206-C001 | Communication Error Between Outdoor Unit Main PBA - Sub PBA | |
206-C002 | FAN PBA communication error | |
206-C003 | INV1 PBA communication error | |
206-C004 | INV2 PBA communication error | |
210 | Can NOT communicate with MCU over 2 min | |
211 | Indoor unit connected with confluence kit without continunity | |
212 | Indoor unit connected with confluence kit and setting address was overlapped more than 3 | |
213 | MCU address not matched with indoor unit address | |
214 | MCU address not matched with outdoor unit address | |
215 | Rotary switch for indoor unit address in MCU was over lapped among MCUs | |
216 | DIP switch for indoor unit setting was ON position even though indoor unit was not connected | |
217 | DIP switch for indoor unit setting was OFF position even though indoor unit was connected | |
218 | Setting number of indoor unit in MCU is larger than installed indoor units | |
219 | Error on temperature sensor located on MCU intercooler inlet (Short or Open)
MCU Over Cooling In Sensor Open/Short |
|
220 | Error on temperature sensor located on MCU intercooler outlet (Short or Open)
MCU Over Cooling Out Sensor Open/Short |
|
221 | OUT temperature SENSOR ERROR (OPEN/SHORT)
- ERROR LEVEL: more than 4.9V(-50oC), less than 0.4V(93oC) |
|
226 | OUT_temperature temperature Sensor breakaway Error | |
231 | COND_OUT Main temperature SENSOR ERROR (OPEN/SHORT)
- ERROR LEVEL: More than 4.9V(-50oC), less than 0.4V(93oC)” |
|
236 | COND_OUT Sub1 temperature SENSOR ERROR (OPEN/SHORT)
- ERROR LEVEL: More than 4.9V(-50oC), less 0.4V(93oC)” |
|
237 | COND temperature SENSOR ERROR (OPEN/SHORT)
- ERROR LEVEL: More than 4.9V(-50oC), less than 0.4V(93oC) |
|
241 | COND_MID or COND OUT Sensor of Outdoor Unit breakaway Error | |
242 | Outdoor Unit Heater Error | |
246 | COND_OUT 1 breakaway | |
251 | PWM DISCHARGE temperature SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect Outdoor temperature more than -10oC - ERROR LEVEL: More than 4.95V(-30’C), less than 0.5V(151’C) |
|
256 | Fixed COMP 1 DCHRG SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect Outdoor temperature more than - ERROR LEVEL: More than 4.95V(-30’C), less than 0.5V(151’C) |
|
257 | Fixed COMP 2 DCHRG SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect Outdoor temperature more than -10oC - ERROR LEVEL: more than 4.95V(-30’C),less than 0.5V(151’C)” |
|
258 | Fixed COMP 3 DCHRG SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: Outdoor temperature more than -10 detect oC - ERROR LEVEL: more than 4.95V(-30’C),less than 0.5V(151’C) |
|
261 | Digital COMP_discharge Sensor breakaway Error | |
262 | Fixd COMP1_discharge Sensor breakaway Error | |
263 | Fixd COMP2_discharge Sensor breakaway Error | |
264 | Fixd COMP3_discharge Sensor breakaway Error | |
265 | SUMP temperature sensor breakaway (Main) | |
266 | SUMP temperature sensor breakaway (Sub1) | |
267 | High Pressure SENSOR breakaway ERROR | |
268 | SUMP temperature sensor breakaway (Sub3) | |
269 | SUCTION Sensor breakaway | |
271 | Digital COMP Sump_temperature Digital SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect outdoor temperature -10oC - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” |
|
276 | FIXED COMP1 Sump_temperature SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect outdoor temperature more than -10oC - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” |
|
277 | FIXED COMP2 Sump_temperature SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect outdoor temperature -10oC - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C)” |
|
278 | FIXED COMP3 Sump_temperature FIXED 3 SENSOR ERROR (OPEN/SHORT)
- ERROR detect Condition: detect outdoor temperature more than -10oC - ERROR LEVEL: more than 4.95V(-30’C), less than 0.5V(151’C) |
|
291 | High pressure SENSOR ERROR (OPEN/SHORT) while in operating COMP only, detect
(shortError: less than 0.4v, Error detect), (OPENError: over 4.2v, Error detect) |
|
296 | Low Pressure SENSOR ERROR (OPEN/SHORT) while in operating COMP only, detect
(shortError: less than 0.4v, Error detect), (OPENError:over 4.7v, Error detect) |
|
301 | High Pressure SENSOR breakaway ERROR | |
306 | Low Pressure SENSOR breakaway ERROR | |
307 | Oil Balance Sensor SHORT/OPEN | |
308 | SUCTION Sensor SHORT/OPEN | |
309 | Oil Balace Sensor2 Sensor SHORT/OPEN | |
310 | Oil Balance Sensor3 Sensor SHORT/OPEN | |
311 | Double pipe Sensor SHORT/OPEN | |
312 | Main Cooling Sol Valve Open Error | |
313 | 4-Way Valve operation Error | |
314 | Oil Balace Sensor4 SHORT/OPEN | |
315 | CT1 Sensor Short or Open | |
316 | CT2 Sensor Short or Open | |
317 | CT3 Sensor Short or Open | |
320 | OLP Sensor SHORT / OPEN | |
321 | EVI INLET Sensor SHORT/OPEN | |
322 | EVI OUTLET Sensor SHORT/OPEN | |
323 | Error on suction sensor 2 (Short or Open) | |
324 | Outdoor Unit Fan Motor Current Sensor SHORT / OPEN | |
325 | Outdoor Unit Fan2 Motor Current Sensor SHORT / OPEN | |
330 | Outdoor plumbing inlet sensor out 0 time (TA_0) | |
331 | Outdoor sensor out once the entrance pipe (TA_1) | |
332 | 2, the inlet pipe outdoor sensor out (TA_2) | |
333 | Three times the inlet pipe outdoor sensor out (TA_3) | |
334 | Outdoor four times the inlet pipe sensor out (TA_4) | |
335 | Outdoor pipe exit sensor out 0 time (TB_0) | |
336 | 1 outdoor sensor out pipe outlet (TB_1) | |
337 | Outdoor sensor out two times pipe outlet (TB_2) | |
338 | Outdoor sensor out three times pipe outlet (TB_3) | |
339 | Outdoor sensor out four pipe outlet (TB_4) | |
346 | Error due to operation failure of Fan2 | |
347 | Motor wire of Fan2 is not connected | |
348 | Lock error on Fan2 of outdoor unit | |
353 | Error due to overheated motor of outdoor unit’s Fan2 | |
355 | Error due to overheated IPM of Fan2 | |
361 | 2 CT1 inverter compressor start failure, or a low-current | |
364 | Error due to over-current of inverter compressor 2. 2 DC Peak Inverter compressor stop | |
365 | V-limit error of inverter compressor 2. 2 inverter compressor overload stops (30A or more) | |
366 | Error due to over voltage /low voltage of inverter PBA2. Less than 2 DC Link Voltage 150V 410V inverter over | |
367 | Error due to unconnected wire of compressor 2. Inverter compressor rotation over 2 Wire dependence or compressor | |
368 | Output current sensor error of inverter PBA2. 2 Comp inverter current sensor error | |
369 | DC voltage sensor error of inverter PBA2. 2 DC Link Inverter Sensor Error | |
371 | 2 inverter outdoor unit EEPROM Read / Write error (OTP error) | |
374 | Heat sink temperature sensor error of inverter PBA2. 2 inverter heat sink temperature sensor error | |
378 | Hall IC connection error of Fan2. Outdoor fan 2 IPM H / W OC | |
385 | Error due to input current of inverter 2. 2 inverter input current sensor Error | |
386 | Over-voltage/low-voltage error of Fan2 | |
387 | Outdoor fan 2 Hall Sensor Error | |
389 | V-limit error on Fan2 of compressor | |
391 | Fan Controller 2 EEPROM Read / Write Error | |
393 | Output current sensor error of Fan2. Fan Controller 2 Current sensor error | |
396 | DC voltage sensor error of Fan2. Fan Controller 2 DC Link sensor error | |
399 | Heat sink temperature sensor error of Fan2. 2 fan controller heat sink temperature sensor error | |
400 | Error due to overheat caused by contact failure on IPM of Inverter PBA2 | |
401 | Outdoor Freezing detect 1 | |
402 | Outdoor Freezing detect 2 | |
403 | Outdoor Freezing detect 3 - Freeze COMP DOWN | |
404 | Outdoor overload 1 Protection Control Error | |
405 | Outdoor overload 2 Protection Control Error | |
406 | Outdoor overload 3 Protection Control Error | |
407 | COMP down due to High PressureSensor Protection Control 1 | |
408 | COMP down due to High PressureSensor Protection Control 2 | |
409 | COMP down due to High PressureSensor Protection Control 3 | |
410 | COMP down due to Low PressureSensor Protection Control 1 | |
411 | COMP down due to Low PressureSensor Protection Control 2 | |
412 | COMP down due to Low PressureSensor Protection Control 3 | |
413 | Outdoor SUMP DOWN_1 Protection Control | |
414 | Outdoor SUMP DOWN_2 Protection Control | |
415 | Outdoor SUMP DOWN_3 Protection Control | |
416 | Outdoor DischargeTemperature_1 Protection Control | |
417 | Outdoor DischargeTemperature_2 Protection Control | |
418 | Outdoor DischargeTemperature_3 Protection Control | |
419 | Outdoor EEV#1 opening 6th Self-Check Error | |
420 | Outdoor EEV#2 opening 6th Self-Check Error | |
421 | Outdoor EEV#3 opening 6th Self-Check Error | |
422 | Outdoor EEV#1 closing 6th Self-Check Error | |
423 | Outdoor EEV#2 closing 6th Self-Check Error | |
424 | Outdoor EEV#3 closing 6th Self-Check Error | |
425 | Outdoor Reverse Phase or Missing Phase detect 1 Error | |
426 | Outdoor Reverse Phase or Missing Phase detect 2 Error | |
427 | Outdoor Reverse Phase or Missing Phase detect 3 Error | |
428 | COMP down by Compression Ratio control Error 1 | |
429 | COMP down by Compression Ratio control Error 2 | |
430 | COMP down by Compression Ratio control Error 3 | |
431 | Oil Balance Valve1 Error | |
432 | Oil Balance Valve2 Error | |
433 | Oil Balance Valve3 Error | |
434 | Oil Balance Valve opening Error (In DVM PLUS 2, HotGasValve Opening Error) | |
435 | Water Cooling Flow Switch Error | |
436 | Evaporator Protect for Freeze and Burst Error | |
437 | Oil Balance Valve Closing Error(In DVM PLUS 2, HotGasValve Opening Error) | |
438 | EVI EEV Opening Error | |
439 | Error due to refrigerant leakage | |
440 | Forbid Heat mode operation when outdoor temperature is over 30oC | |
441 | Forbid Cooling Mode when OutdoorTemperature ia less than -5oC | |
442 | Forbid an operation during heat mode with refrigerant charging operation when out door temperature
is over 15oC |
|
443 | Before Cooling working, less than Low Pressure 1K(inability to re-operate) | |
445 | CCH is detached. CCH Self-Check Error (CCH malfunction Or Sump Sensor miss connection) | |
446 | Error due to operation failure of Fan1. Fan Controller 1 Fan failed maneuver | |
447 | Motor wire of Fan1 is not connected. Fan controller wiring 1 Wire U.S. | |
448 | Lock error on Fan1. Fan Controller 1 Lock error | |
450 | COND High Temperature(Protection Control) Every Time | |
451 | Low Pressure Switch Low Pressure(Protection Control) | |
452 | Instant power off Error (delete when COMP re-operate)
Outdoor Zero-Crossing Error |
|
453 | Outdoor Fan high temperaturet Error | |
454 | OutdoorFan RPM Error (more than 2500rpm and the difference that target velocity compare with practical
velocity is more than 100rpm per 10SEC, more than 10 times) |
|
455 | OutdoorFan IPM(Internal PCB Module) high temperature Error | |
456 | OutdoorFan Overcurrent Error | |
457 | OutdoorFan Reversed direction of the wind Error | |
458 | Outdoor unit Fan (Fan Error) Or CT1 over currency | |
459 | Outdoor unit IPM Fault Error Or CT2 over currency | |
460 | Outdoor unit communication-power disconnected detect Or CT3 over currency | |
461 | Inverter COMP operating failure Or CT1 low currency | |
462 | All currency control COMP Stop Or CT2 low currency | |
463 | OLP Temperature control COMP Stop Or CT3 low currency | |
464 | DC Peak COMP stop | |
465 | COMP Overload stop(over 30A) | |
466 | DC Link voltage less than 150V, over 410V | |
467 | COMP revolute error Or COMP Wire In-connection | |
468 | Inv Comp Current Sensor Error | |
469 | DC Link Sensor Error | |
470 | Outdoor unit EEPROM Read/Write Error | |
471 | Outdoor unit EEPROM Read/Write Error(OTP error) | |
472 | Outdoor unit Zero crossing Error | |
473 | Inverter Comp Lock Error | |
474 | Heat sink temperature sensor error of inverter PBA1 | |
475 | Outdoor unit BLDC Fan 2 Error Or
OutdoorFan2 RPM Error (more than 2500rpm and the difference that target velocity compare with practical velocity is more than 100rpm per 10SEC, more than 10 times) |
|
476 | 4wAY Error detect | Self-Check, After 6 times, COMP DOWN |
477 | Control for protecting liquid refrigerant | |
478 | Error due to over current of Fan1. OutdoorFan IPM H/W OC | |
479 | 4WAY miss connection detect Error | |
480 | Fixed Comp 1 Stege OLP Protection Control(leakage for refrigerant Error) | |
481 | Comp1 operating Error | |
482 | Comp2 operating Error | |
483 | Overvoltage of H/W Detect DC Link | |
484 | PFC Overload (overcurrent) Error | |
485 | Error due to input current of inverter 1. Input current Sensor Error | |
486 | Error due to over voltage/low voltage of Fan. Outdoor Fan DC-Link Voltage Under/Over Error | |
487 | Hall IC error of Fan1. Outdoor Fan Hall Sensor Error | |
489 | V-limit error on Fan1 of compressor | |
490 | Outdoor Temperature 0 degrees & Indoor Temperature less than 0 degrees prohibition to operate | ERV Ventilation System |
491 | Fan Controller1 EEPROM Read/Write Error | |
492 | Outdoor Fan2 IPM H/W OC | |
493 | Output current sensor error of Fan1. Fan Controller1 Current Sensor Error | |
494 | Delayed time Error due to OutdoorFan2 Fan Error | |
495 | Outdoor Fan2 Overheat Error | |
496 | DC voltage sensor error of Fan1. Fan Controller1 DC Link Sensor Error | |
497 | Outdoor Fan2 Overcurrent Error | |
498 | Outdoor Fan2 IPM(Internal PCB Module) Overheat Error | |
499 | Heat sink temperature sensor error of Fan1. Fan Controller1 Heat Sink Temp Sensor Error | |
500 | IPM Overheat Error for Inverter COMP | |
503 | Error due to alert the user to check if the service valve is closed | |
504 | Error due to self diagnosis of compressor operation | |
505 | Error due to self diagnosis of high pressure sensor | |
506 | Error due to self diagnosis of low pressure sensor | |
512 | RESERVED(DMS-SNET3 Error) | |
551 | Defrost working | |
552 | Low Discharge Pressure | |
553 | Equability operation | |
554 | loading_failure / total Leakage of Refrigerant of Outdoor Unit | |
555 | Recovery of oil | |
556 | Outdoor Unit power set option Error | |
557 | When DPM mode, Product option are not same between indoor units | |
559 | Indoor Unit operating stop due to detect unknown error in Outdoor Unit | |
560 | Outdoor Unit Switch option setting error(not applied) | |
561 | Outdoor Unit SA(SUPPLY AIR) FAN RPM | |
562 | Outdoor Unit RA(ROOM AIR) FAN RPM | |
563 | Indoor Unit mixed install error | |
564 | IAQ Clean Fan Error | |
565 | Miss connection Error between Comp and power wire - power line of Eva1 connect with Comp2 or
power line of Eva2 connect with Comp1 |
|
570 | Boot Code Check FAIL | |
573 | Error due to using single type outdoor unit in a module installation | |
574 | Total Leakage of Refrigerant of Outdoor Unit 2 | |
575 | Total Leakage of Refrigerant of Outdoor Unit 3 (Comp1, Comp2 bot detected) | |
601 | Wired LCD (controller) <-> Indoor Unit Communication Error | |
602 | Master Wire LCD <-> Slave Wire LCD Communication Error | |
603 | Communication Packet Error (Baudrate / different communication type) | |
604 | Wired LCD (controller) <-> Indoor Unit Tracking Error over 10 times | |
605 | 7 Day Scheduler <-> Wire LCD ,CAUR Communication Error | |
606 | Wire LCD COM1/COM2 Cross Install Error | |
607 | Wile Wire LCD Master-Master installation, Communication Error | |
608 | External linkage ERV Controller No installation Error | |
609 | External linkage Indoor No installation Error | |
610 | CAUR <-> Transmitter Communication Error | |
611 | DMS <-> CAUR Communication Error | |
612 | DMS <-> PEAK Transmitter Communication Error | |
613 | DMS <-> PIM/SIM Transmitter Communication Error | |
614 | Amount of electricity system <-> PIM/SIM Transmitter Communication Error | |
615 | Transmitter <-> Indoor unit Communication Error (After complete Transmitter Tracking, for 2min some indoor
unit can’t communicate.) |
|
616 | Transmitter <-> Outdoor unit Communication Error (After completeTransmitter Tracking, for 2min outdoor
unit can’t communicate) |
|
617 | Peak power Transmitter <-> Demand Controller Communication Error, Demand Transmitter
<-> Amount of eletricity system communication Error |
|
618 | ERV Controller+indoor unit (16EA) over Max install number Error | |
619 | Celcius/Fahrenheit indoor unit mixed install error | |
620 | New wired remote controller "Celcius/Fahrenheit" set error (DIP S/W #4 set error) | |
621 | New Wire Remote controller Master/Slave Dip Switch option Set Error (Difference with set option of
Master and Slave) |
|
622 | Demand Controller / select the type of amount of electricity system Error | |
623 | Demand Transmitter PT / CT ratio set Error | |
624 | Demand Transmitter data receive error from amount of electricity | |
625 | Master DMS ? Slave DMS Communication Error | |
626 | ERV linkage wire remote controller(AWR-WE00) ERV separate installation Error (not connect indoor unit
and, only ERV be installed) indoor unit linkage wire remocontroller(AWR-VH10) indoor unit separate installation Error (not connect indoor unit and, only ERV be installed) |
|
627 | While in linkage controll Master/Slave Wire Remote controller, Slave Wire Remote controller 2EA installation
Error (Installing Wire Remocontroller set slave in Master Wire Remocontroller 2EA at the same time) |
|
628 | DMS <-> Transmitter Communication Error | |
629 | DMS <-> DDC Communication Error | |
630 | ERV wire remote controller normal ventilation option set Error
- Check normal ventilation option set only. - ERV normal ventilation No option, use Wire Remote controller option normal ventilation |
|
631 | ERVWire Remote controller auto ventilation option set Error
- Check set auto ventilation only - ERV auto ventilation no option, use wire remote controller auto ventilation |
|
632 | Error when input the pulse except set the value of Pulse Width by PIM
1. less than 20ms , 2. over 400ms , 3. over range of set pulse width, 4. repeated purse over 3min |
|
652 | While COM 1 Dual Master installation Commnunication Error | |
653 | Temperature Sensor Open/Short Error | |
654 | FRAM Error or damper Error(ERV model) | |
655 | RESERVED(DMS-SNET3 Error) | |
656 | RESERVED(DMS-SNET3 Error) | |
701 | Float 1st | |
702 | Indoor EEV clsosing 1st | |
703 | Indoor EEV opening 1st | |
720 | Outdoor EEV#1 opening Self-Check Every time error | |
721 | Outdoor EEV#2 opening Self-Check Every time error | |
722 | Outdoor EEV#3 opening Self-Check Every time error | |
723 | Outdoor EEV#1 closing Self-Check Every time error | |
724 | Outdoor EEV#2 closing Self-Check Every time error | |
725 | Outdoor EEV#3 closing Self-Check Every time error | |
768 | RESERVED(DMS-SNET3) | |
801 | [GHP-R410A] communication error : “IF <-> Outdoor unit” : Disconnection | |
802 | [GHP-R410A] communication error : “Outdoor unit <-> IF” : Disconnection | |
803 | [GHP-R410A] communication error : “IF <-> Indoor unit” some disconnect in Indoor unit (communicating) | |
804 | [GHP-R410A] communication error : Among outdoor unit | |
805 | [GHP-R410A] Error setting outdoor unit organization | |
806 | [GHP-R410A] Remocon Sensor disconnect/short circuit | |
807 | [GHP-R410A] outdoor liquid pipe Sensor disconnect/short circuit | |
808 | [GHP-R410A] outdoor Unit - overcooling heat exchanger entry temp thermystor disconnect/short circuit | |
809 | [GHP-R410A]COMP suction temp overheat | |
810 | [GHP-R410A] COMP suction superheat not soar | |
811 | [GHP-R410A] refrigerant high pressure Switch disconnect | |
812 | [GHP-R410A] Gas EEV Output error | |
813 | [GHP-R410A] refrigerant low pressure Sensor error(2nd) | |
814 | [GHP-R410A] refrigerant high pressure Sensor error 1 | |
815 | [GHP-R410A] refrigerant high pressure Sensor error 2 (value of high pressure sensor less
than standard low pressure) |
|
816 | [GHP-R410A] Water Pump operation failure | |
817 | [GHP-R410A] Water Pump a number of revolute error | |
818 | [GHP-R410A] IPM(outdoor unit FAN operating Driver) error | |
819 | [GHP-R410A] outdoor heat exchange Fan 1 operating failure | |
820 | [GHP-R410A] outdoor heat exchange Fan 2 operating failure | |
821 | [GHP-R410A] outdoor heat exchange Fan 3 operating failure | |
822 | [GHP-R410A] outdoor heat exchange Fan 1 a number of revolute error | |
823 | [GHP-R410A] outdoor heat exchange Fan 2 a number of revolute error | |
824 | [GHP-R410A] outdoor heat exchange Fan 3 a number of revolute error | |
825 | [GHP-R410A] outdoor Unit - heat exchange Fan error | |
826 | [GHP-R410A] outdoor Unit - Accum exit temp thermystor 1 disconnect/short circuit | |
827 | [GHP-R410A] outdoor Unit - Accum exit temp thermystor 2 disconnect/short circuit | |
828 | [GHP-R410A] outdoor unit Unit - refrigerant low pressure Switch disconnect | |
829 | [GHP-R410A] refrigerant low pressure error | |
830 | [GHP-R410A] three phase error | |
831 | [GHP-R410A] one phase power part error | |
832 | [GHP-R410A] Main - Sub MICOM Program Version Unmatch | |
833 | [GHP-R410A] indoor unit connection number Over | |
834 | [GHP-R410A] indoor unit connection capacity Over | |
835 | [GHP-R410A] outdoor-indoor connection Unmatch | |
836 | [GHP-R410A] Outdoor Unit -Regular Inspection | |
837 | [GHP-R410A] Refrigerant High pressure error 1 | |
838 | [GHP-R410A] Refrigerant High pressure error 2 | |
841 | [GHP-R410A] Outdoor Unit Gas Temp Thermistor short/disconnection | |
843 | [GHP-R410A] Engine water temp Sensor short/disconnection | |
844 | [GHP-R410A] Engine discharge temp Sensor disconnection | |
845 | [GHP-R410A] Engine fluid pressure error | |
846 | [GHP-R410A] Engine Fluid pressure Switch disconnected | |
847 | [GHP-R410A] Engine over revolute 1 | |
848 | [GHP-R410A] Engine over revolute 2 | |
849 | [GHP-R410A] Starter Error | |
850 | [GHP-R410A] Engine a number of revolute control error | |
851 | [GHP-R410A] Engine Stop | |
852 | [GHP-R410A] IGUNAITA(firer) low voltage | |
853 | [GHP-R410A] IGUNAITA(firer) disconnect | |
854 | [GHP-R410A] IGUNAITA(firer) over voltage | |
855 | [GHP-R410A] Engine discharge temp Error | |
856 | [GHP-R410A] Engine water temp overheat | |
857 | [GHP-R410A] Engine operation failure | |
858 | [GHP-R410A] Engine cooling | |
859 | [GHP-R410A] Engine insufficient operating revolute | |
860 | [GHP-R410A] Engine a number of revolute Haunting Error | |
861 | [GHP-R410A] COMP discharge temperature overheat | |
862 | [GHP-R410A] Compressor Discharge temperature Sensor1 short/disconnection | |
863 | [GHP-R410A] Compressor Discharge temperature Sensor2 short/disconnection | |
864 | [GHP-R410A] Compressor Discharge temperature Sensor3 short/disconnection | |
865 | [GHP-R410A] Compressor Discharge temperature Sensor4 short/disconnection | |
866 | [GHP-R410A] Compressor nhale temperature Sensor1 short/disconnection | |
867 | [GHP-R410A] Compressor suction temperature Sensor2 short/disconnection | |
868 | [GHP-R22] Outdoor Unit - Accum Entrance Temperature Sensor short/disconnection | |
869 | [GHP-R22] Outdoor Unit - refrigerants Gas pipe temperature Sensor short/disconnection | |
870 | [GHP-R22] Outdoor Unit - comp lubricating oil insufficiency error | |
871 | [GHP-R22] Outdoor Unit - Refrigerant overfill error | |
872 | [GHP-R22] Outdoor Unit - Compressor induction temperature error | |
873 | [GHP-R22] Engine cooling system Error | |
874 | [GHP-R22] Engine Oil System error | |
875 | [GHP-R22] Engine power system Error | |
876 | [GHP-R22] Engine operating/control system Error | |
880 | [GHP-R410A] Outdoor Unit - Engine Temp of Cooling water low | |
881 | [GHP-R410A] Outdoor Unit - leakage of Engine oil | |
882 | [GHP-R410A] Outdoor Unit - Lack of Comp oil | |
883 | [GHP-R410A] Outdoor Unit - starter Trans voltage short | |
901 | Water Inlet Sensor(Tw1) SHORT / OPEN | |
902 | Water Outlet Sensor(Tw3) SHORT / OPEN | |
903 | PHE Sensor(Tw2) SHORT / OPEN | |
904 | Water TANK Sensor SHORT / OPEN | |
905 | SOLAR Sensor SHORT / OPEN | |
911 | Flow Swtich Open Error | |
912 | Flow Swtich Close Error |