Difference between revisions of "CoolMasterNet FW Update"

From CoolAutomation Wiki
Jump to navigation Jump to search
 
(38 intermediate revisions by 2 users not shown)
Line 1: Line 1:
* Download and Install '''Cool Automation SW Package''':
+
__FORCETOC__
[http://coolautomation.com/lib/utilities/update-utility/CoolAutomation-170810.exe CoolAutomation-170810.exe]
+
== Firmware update ==
* Get CoolMasterNet FW Image. Latest FW Image can be downloaded here:
+
* Download and Install [https://support.coolautomation.com/hc/en-us/articles/5139558696733-CoolAutomation-ToolBox '''CoolAutomation ToolBox''']
{| class="wikitable"
+
 
|-
+
== Forced BOOT Mode ==
! Image
+
In certain situations, like for instance in case of power outage during regular FW update, CoolMasterNet can become irresponsible due to a luck of proper FW. In this case, to recover CoolMasterNet, it has to be updated via forced BOOT mode.
! Version
+
 
! Date
+
* Set all dip switches on R line into ON position (up). Remember previous status of R dip switches. Do not change dip switches on P,Q,S lines
! Key Features
+
[[File:CM5-dips-forced-boot.png|200px]]
! Status
+
* Power reset CoolMasterNet device. It will stay in forced BOOT mode.
|-
+
* Run FW Update.
| <htmltag tagname="a" href="http://coolautomation.com/lib/firmware/CMNET/0.4.8/CM5-0.4.8.INC" download>CM5-0.4.8.INC</htmltag>
+
* After the FW Update is done, restore R line dip switches and power reset CoolMasterNet.
| 0.4.8
+
 
| 03 Jun 2017
+
== Safe Mode ==
| Fixes,Samsung improvements,PRO rework,Hitachi F support,Simulation feed,
+
Sometimes due to wrong configurations made in CoolMasterNet it can become irresponsible. In this case CoolMasterNet can be powered up in Safe Mode.
| '''Stable'''
+
* Set all dip switches on Q line into ON position (up). Remember previous status of Q dip switches. Do not change dip switches on P,R,S lines
|-
+
[[File:CM5-dips-safe-mode.png|200px]]
| <htmltag tagname="a" href="http://coolautomation.com/lib/firmware/CMNET/0.4.6/CM5-0.4.6.INC" download>CM5-0.4.6.INC</htmltag>
+
* Power reset CoolMasterNet device. It will stay in SAFE MODE.
| 0.4.6
+
* In Safe Mode CoolMasterNet can interface via RS232 or USB connection only. ETH and HVAC Lines are disabled.
| 25 Jan 2017
+
* After configurations are done, restore Q line dip switches and power reset CoolMasterNet.
| Fixes,Reboot on Assert,Greensys,UMM,DHCP recovery,HHAUX support
 
| '''Stable'''
 
|-
 
|}
 
<br>
 
* Connect CoolMasterNet to USB. If it is the first time connection, USB driver will be installed
 
[[File:CM5-USB-prog-connection.png]]
 
* Run '''CoolAutomation Firmware Updater'''
 
* Load FW Image
 
* Click Update Firmware
 
[[File:FW_Updatrer.gif]]
 

Latest revision as of 23:44, 26 October 2024

Firmware update

Forced BOOT Mode

In certain situations, like for instance in case of power outage during regular FW update, CoolMasterNet can become irresponsible due to a luck of proper FW. In this case, to recover CoolMasterNet, it has to be updated via forced BOOT mode.

  • Set all dip switches on R line into ON position (up). Remember previous status of R dip switches. Do not change dip switches on P,Q,S lines

CM5-dips-forced-boot.png

  • Power reset CoolMasterNet device. It will stay in forced BOOT mode.
  • Run FW Update.
  • After the FW Update is done, restore R line dip switches and power reset CoolMasterNet.

Safe Mode

Sometimes due to wrong configurations made in CoolMasterNet it can become irresponsible. In this case CoolMasterNet can be powered up in Safe Mode.

  • Set all dip switches on Q line into ON position (up). Remember previous status of Q dip switches. Do not change dip switches on P,R,S lines

CM5-dips-safe-mode.png

  • Power reset CoolMasterNet device. It will stay in SAFE MODE.
  • In Safe Mode CoolMasterNet can interface via RS232 or USB connection only. ETH and HVAC Lines are disabled.
  • After configurations are done, restore Q line dip switches and power reset CoolMasterNet.