== Setting Indoor Group Address ==
 
== Setting Indoor Group Address ==
Indoor Group Address is required for proper CoolMasterNet operation. Without Group Address Indoor unit is not visible and can not be controlled by CoolMasterNet. Group Address is set with wired remote controller. Here is a simple sequence of operations for Daikin BRCE61 wired remote controller to set group address.
+
Indoor Group Address is required for proper CoolMasterNet operation. Without Group Address Indoor unit is not visible and can not be controlled by CoolMasterNet. Group Address is set with wired remote controller. Here is a simple sequence of operations for Daikin BRCE61 wired remote controller to set Group Address.
 
+
* Press and hold ''Cancel'' button for a few seconds<br>
1. Press and hold the ''Cancel'' button for a few seconds<br>
+
[[File:BRC1E61-buttons.gif]]
2. Scroll down to ''Group No. setting'' function and press ''Menu/Enter'' button<br>
+
* Scroll down to ''Group No. setting'' function and press ''Menu/Enter'' button<br>
3. Program Group Address and then press ''Menu/Enter'' to save address<br>  
+
[[File:BRC1E61-group-address-menu.gif]]
 +
* Program Group Address and then press ''Menu/Enter'' to save address<br>  
 
   
 
   
 
'''Remember if Indoor unit can not see a CoolMasterNet you won't have the Group Address menu option. So make sure the CoolMasterNet is wired to F1 F2 HVAC line and powered.'''
 
'''Remember if Indoor unit can not see a CoolMasterNet you won't have the Group Address menu option. So make sure the CoolMasterNet is wired to F1 F2 HVAC line and powered.'''

Revision as of 01:03, 5 December 2015

Setting Indoor Group Address

Indoor Group Address is required for proper CoolMasterNet operation. Without Group Address Indoor unit is not visible and can not be controlled by CoolMasterNet. Group Address is set with wired remote controller. Here is a simple sequence of operations for Daikin BRCE61 wired remote controller to set Group Address.

  • Press and hold Cancel button for a few seconds

BRC1E61-buttons.gif

  • Scroll down to Group No. setting function and press Menu/Enter button

BRC1E61-group-address-menu.gif

  • Program Group Address and then press Menu/Enter to save address

Remember if Indoor unit can not see a CoolMasterNet you won't have the Group Address menu option. So make sure the CoolMasterNet is wired to F1 F2 HVAC line and powered.