Modbus RTU Configuration
CoolMasterNet Modbus RTU is activated with below command:
>line type L3 CG5
OK, Boot Required!
>
|
CoolMasterNet has to be restarted to run Modbus RTU for the first time.
To quire current Modbus RTU configuration use line command:
>line
L1: SA Master U00/G00 myid:E5
Tx:0/0 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L2: DK Slave U00/G00 myid:0B
Tx:0/0 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L3: CG5 Modbus Address:0x40(64) 9600_8N1
Tx:0/0 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L4: MH SLink:N U00/G00 myid:C900
Tx:0/2 Rx:0/2 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L5: Unused
Tx:0/0 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L6: Unused
Tx:0/0 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L7: LG Master U00/G00
Tx:983/1066 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
L8: Unused
Tx:0/0 Rx:0/0 TO:0/0 CS:0/0 Col:0/0 NAK:0/0
OK
>
|
The rest is similar between Modbus RTU and Modbus IP. Follow the link to VA Concept.