CoolMasterNet FAQ
Contents
General
How to make connection from PC
We suggest to use Putty a simple and free terminal program. Connection can be done via RS232 or TCP/IP.
Networking
How to change IP address and/or other network settings
IP network configuration is made with ifconfig command described in PRM document.
Modbus RTU
How to enable Modbus RTU on line L3
Below command will enable Modbus RTU functionality on line L3.
>line type L3 CG5 |
CG5 stands for "CoolGate5", which is a new Modbus RTU implementation in CoolMasterNet (see details). There is also a CG4 option which will enable an implementation backward compatible with a legacy "CoolGate" device.
How to query or change Modbus Slave Address
Modbus Slave Address is available via line command.
>line
L1: SA U00/G05 myid:E5 Simul(5) |
To change Modbus Slave Address use line command as shown below:
>line myid L3 50 |
This command will set Modbus Slave Address 0x50(hexadecimal)