Control Wiring Termination
In some cases with relatively big HVAC systems, where the total length of the wiring is high, control wire termination may be required. Termination can also be helpful if a control communication is noisy as a result of external electromagnetic influence. Termination can be easily made on CoolMasterNet side. To do it turn ON DIP Switch S2 - for line L1 and/or S3 - for line L2 as shown below. Rest of the DIP Switches should not be changed.
Malfunction Code |
Category | Content of Abnormality | Leading Cause | Cool Automation Encoding | |
---|---|---|---|---|---|
01 | Indoor Unit | Activation of Protection Device (Float Switch) | Activation of Float Switch (High Water Level in Drain Pan, Abnormality of Drain Pipe, Float Switch or Drain Pan) |
01 | 01 |
02 | Outdoor Unit | Activation of Protection Device (High Pressure Cut) |
Activation of PSH (Pipe Clogging, Excessive Refrigerant, Inert Gas Mixing) |
02 | 02 |
03 | Transmission | Abnormality between Indoor and Outdoor | Incorrect Wiring, Loose Terminals, Disconnect Wire, Blowout of Fuse, Outdoor Unit Power OFF |
03 | 03 |
04 | Transmission | Abnormality between Inverter PCB and Outdoor PCB | Inverter PCB - Outdoor PCB Transmission Failure (Loose Connector, Wire Breaking, Blowout of Fuse) |
04 | 04 |
04 | Transmission | Abnormality between Fan Controller and Outdoor PCB | Fan Controller - Outdoor PCB Transmission Failure (Loose Connector, Wire Breaking, Blowout of Fuse) |
04 | 04 |
05 | Supply Phase | Supply Phase | Incorrect Power Source, Connection to Reversed Phase, Open-Phase |
05 | 05 |
06 | Voltage | Abnormal Inverter Voltage Abnormal Fan Controller Voltage |
Outdoor Voltage Drop, Insufficient Power Capacity | 06 | 06 |
07 | Cycle | Decrease in Discharge Gas Superheat | Excessive Refrigerant Charge, Failure of Thermistor, Incorrect Wiring, Incorrect Piping Connection, Expansion Valve Locking at Opened Position (Disconnect Connector) |
07 | 07 |
08 | Cycle | Increase in Discharge Gas Temperature | Insufficient Refrigerant Charge, Pipe Clogging, Failure of Thermistor, Incorrect Wiring, Incorrect Piping Connection, Expansion Valve Locking at Closed Position (Disconnect Connector) |
08 | 08 |
0A | Transmission | Abnormality between Outdoor and Outdoor | Incorrect Wiring, Breaking Wire, Loose Terminals | OA | 0A |
0b | Outdoor Unit | Incorrect Outdoor Unit Address Setting | Incorrect Outdoor Unit Address Setting | Ob | Ob |
0C | Outdoor Unit | Incorrect Outdoor Unit Main Unit Setting | Two (or more) Outdoor Units Set as “Main Unit” | OC | OC |
11 | Sensor on Indoor Unit | Inlet Air Thermistor | Incorrect Wiring, Disconnecting Wiring Breaking Wire, Short Circuit |
11 | 11 |
12 | Sensor on Indoor Unit | Outlet Air Thermistor | Incorrect Wiring, Disconnecting Wiring Breaking Wire, Short Circuit |
12 | 12 |
13 | Sensor on Indoor Unit | Freeze Protection Thermistor | Incorrect Wiring, Disconnecting Wiring Breaking Wire, Short Circuit |
13 | 13 |
14 | Sensor on Indoor Unit | Gas Piping Thermistor | Incorrect Wiring, Disconnecting Wiring Breaking Wire, Short Circuit |
14 | 14 |
19 | Fan Motor | Activation of Protection Device for Indoor Fan | Fan Motor Overheat, Locking | 19 | 19 |
21 | Sensor on Outdoor Unit | High Pressure Sensor | Incorrect Wiring, Disconnecting Wiring Breaking Wire, Short Circuit |
21 | 21 |
22 | Sensor on Outdoor Unit | Outdoor Air Thermistor | Incorrect Wiring, Disconnecting Wiring Breaking Wire, Short Circuit |
22 | 22 |
23 | Sensor on Outdoor Unit | Discharge Gas Thermistor on Top of Compressor | Incorrect Wiring, Disconnecting Wiring Breaking Wire, Short Circuit |
23 | 23 |
24 | Sensor on Outdoor Unit | Heat Exchanger Liquid Pipe Thermistor | Incorrect Wiring, Disconnecting Wiring Breaking Wire, Short Circuit |
24 | 24 |
25 | Sensor on Outdoor Unit | Heat Exchanger Gas Pipe Thermistor | Incorrect Wiring, Disconnecting Wiring Breaking Wire, Short Circuit |
25 | 25 |
29 | Sensor on Outdoor Unit | Low Pressure Sensor | Incorrect Wiring, Disconnecting Wiring Breaking Wire, Short Circuit |
29 | 29 |
31 | System | Incorrect Capacity Setting of Outdoor Unit Indoor Unit |
Incorrect Capacity Code Setting of Combination Excessive or Insufficient Indoor Unit Total Capacity Code |
31 | 31 |
35 | System | Incorrect Setting of Indoor Unit No. | Duplication of Indoor Unit No. in same Ref. Gr. | 35 | 35 |
36 | System | Incorrect of Indoor Unit Combination | Indoor Unit is Designed for R22 | 36 | 36 |
38 | System | Abnormality of Picking up Circuit for Protection in Outdoor Unit |
Failure of Protection Detecting Device (Incorrect Wiring of Outdoor PCB) |
38 | 38 |
39 | Compressor | Abnormality Running Current at Constant Speed Compressor |
Overcurrent, Blowout Fuse, Current Sensor Failure, Instantaneous Power Failure, Voltage Drop, Abnormal Power Supply |
39 | 39 |
3A | Outdoor Unit | Abnormality of Outdoor Unit Capacity | Outdoor Unit Capacity > 54HP | 3A | 3A |
3b | Outdoor Unit | Incorrect Setting of Outdoor Unit Models Combination or Voltage |
Incorrect Setting of Main and Sub Unit(s) Combination or Voltage |
3b | 3b |
3d | Outdoor Unit | Abnormality Transmission between Main Unit and Sub Unit(s) | Incorrect Wiring, Disconnect Wire, Breaking Wire, PCB Failure |
3d | 3d |
43 | Protection Device | Activation of Low Compression Ratio Protection Device | Defective Compression (Failure of Compressor of Inverter, Loose Power Supply Connection) |
43 | 43 |
44 | Protection Device | Activation of Low Pressure Increase Protection Device | Overload at Cooling, High Temperature at Heating, Expansion Valve Locking (Loose Connector) |
44 | 44 |
45 | Protection Device | Activation of High Pressure Increase Protection Device | Overload Operation (Clogging, Short-Pass), Pipe Clogging, Excessive Refrigerant, Inert Gas Mixing |
45 | 45 |
47 | Protection Device | Activation of Low Pressure Decrease Protection Device (Vacuum Operation Protection) |
Insufficient Refrigerant, Refrigerant Piping, Clogging, Expansion Valve Locking at Open Position (Loose Connector) |
47 | 47 |
48 | Protection Device | Activation of Inverter Overcurrent Protection Device | Overload Operation, Compressor Failure | 48 | 48 |
51 | Sensor | Abnormal Inverter Current Sensor | Current Sensor Failure | 51 | 51 |
53 | Inverter | Inverter Error Signal Detection | Driver IC Error Signal Detection (Protection for Overcurrent, Low Voltage, Short Circuit) |
53 | 53 |
54 | Inverter | Abnormality of Inverter Fin Temperature | Abnormal Inverter Fin Thermistor, Heat Exchanger Clogging, Fan Motor Failure |
54 | 54 |
55 | Inverter | Inverter Failure | Inverter PCB Failure | 55 | 55 |
57 | Fan Controller | Activation of Fan Controller Protection | Driver IC Error Signal Detection (Protection for Overcurrent, Low Voltage, Short Circuit), Instantaneous Overcurrent |
57 | 57 |
5A | Fan Controller | Abnormality of Fan Controller Fin Temperature | Fin Thermistor Failure, Heat Exchanger Clogging, Fan Motor Failure |
5A | 5A |
5B | Fan Controller | Activation of Overcurrent Protection | Fan Motor Failure | 5B | 5B |
5C | Fan Controller | Abnormality of Fan Controller Sensor | Failure of Current Sensor (Instantaneous Overcurrent, Increase of Fin Temperature, Low Voltage, Earth Fault, Step-Out) |
5C | 5C |
EE | Compressor | Compressor Protection Alarm (It is can not be reset from remote Controller) |
This alarm code appears when the following alarms occurs three times within 6 hours. *02, 07, 08, 39, 43 to 45, 47 |
EE | EE |
b1 | Outdoor Unit No. Setting | Incorrect Setting of Unit and Refrigerant Cycle No. | Over 64 Number is Set for Address or Refrigerant Cycle. | b1 | b1 |